Oil & Gas Regulating System
Heating and Pumping Units
Our Oil Pumping and Heating Units are designed to supply fuel oil at pre-determined constant pressure and temperature to ensure efficient combustion. These compact and fully assembled units with all valves, thermostats, pressure gages, pressure switches etc on its own drip tray prevent undesirable variations in temperature caused by heat loss and varying rates of oil flow in long oil lines from heaters located far away. The PH units circulate oil in the ring main at three times of the consumption to provide a stable oil supply system for best combustion results.
Gas Trains For Pressure Reducing System
A gas train consists of Filter, Slam-shut off valve, pressure regulator, safety relief valve & flame arrestor. Filter helps to remove the dust / dirt particles in the gas which may damage the regulator parts. The slam shut off valve normally remains open. Incase the outlet pressure of the regulator exceeds the permissible limits, the slam shut off valve senses it through the impulse line & instantly shuts off the supply to the downstream system. The safety relief valve is provided for additional safety. It is to be set at higher pressure than the slam shut off valve pressure so that the safety relief valve will operate only when slam shut off valve fails to operate. The outlet of the safety relief valve is vented well above the roof.